Commissioning Proline Prosonic Flow W 400 HART
98 Endress+Hauser
Parameter Prerequisite Description Selection / User
entry
Factory setting
Maximum frequency value The Frequency option is
selected in the Operating
mode parameter (→  96)
and a process variable is
selected in the Assign
frequency output parameter
(→  97).
Enter maximum frequency. 0.0 to 10 000 Hz
Measuring value at minimum
frequency
The Frequency option is
selected in the Operating
mode parameter (→  96)
and a process variable is
selected in the Assign
frequency output parameter
(→  97).
Enter measured value for
minimum frequency.
Signed floating-point
number
Depends on country
and nominal
diameter
Measuring value at maximum
frequency
The Frequency option is
selected in the Operating
mode parameter (→  96)
and a process variable is
selected in the Assign
frequency output parameter
(→  97).
Enter measured value for
maximum frequency.
Signed floating-point
number
Depends on country
and nominal
diameter
Failure mode The Frequency option is
selected in the Operating
mode parameter (→  96)
and a process variable is
selected in the Assign
frequency output parameter
(→  97).
Select output behavior in the
event of a device alarm.
Actual value
Defined value
0 Hz
Failure frequency In the Operating mode
parameter (→  96), the
Frequency option is selected,
in the Assign frequency
output parameter (→  97) a
process variable is selected,
and in the Failure mode
parameter, the Defined value
option is selected.
Enter frequency output value
in alarm condition.
0.0 to 12 500.0 Hz
Invert output signal Invert the output signal. No
Yes
* Visibility depends on order options or device settings
Configuring the switch output
Navigation
"Setup" menu → Pulse/frequency/switch output 1 to n
Pulse/frequency/switch output
1 to n
Operating mode
→  99
Switch output function
→  99
Assign diagnostic behavior
→  99
Assign limit
→  99