Proline Prosonic Flow W 400 HART Mounting procedure
Endress+Hauser 21
1
2 × DN 2 × DN
4
A
B
2 × DN
2 × DN
C
3
0…15 × DN
0…15 × DN
0…15 × DN
6
a
b
2
5
A0053788
A Inlet and outlet runs DN 50 to 4000 (2 to 160")
B Inlet and outlet runs DN 15 to 65 (½ to 2½")
C Position of inlet and outlet runs on sensor
1 Single elbow
2 Double elbow (2 × 90° in the same plane, with 0 to 15 x DN between the elbows)
3 Double elbow 3D (2 × 90° in different planes, with 0 to 15 x DN between the elbows)
4 45° bend
5 "2 x 45° bend" option (2 × 45° in the same plane, with 0 to 15 x DN between the elbows)
6a Concentric diameter change (contraction)
6b Concentric diameter change (expansion)
Inlet and outlet runs without FlowDC
Minimum inlet and outlet runs without FlowDC with 1 or 2 sensor sets with different flow
obstructions