Proline Prowirl R 200 HART Commissioning
Endress+Hauser 111
2nd temperature delta heat
→ 112
Fixed process pressure
→ 112
Parameter overview with brief description
Parameter Prerequisite Description Selection / User
entry
Factory setting
External value With order code for "Sensor
version":
• Option "Mass (integrated
temperature measurement)"
or
• Option "Mass (integrated
pressure/temperature
measurement)"
Assign variable from external
device to process variable.
For detailed information
on the calculation of the
measured variables with
steam: → 132
• Off
• Pressure
• Gauge pressure
• Density
• Temperature
• 2nd temperature
delta heat
Off
Atmospheric pressure In the External value
parameter, the Gauge
pressure option is selected.
Enter atmospheric pressure
value to be used for pressure
correction.
Dependency
The unit is taken from the
Pressure unit parameter
0 to 250 bar 1.01325 bar
Delta heat calculation The Delta heat calculation
parameter is visible.
Calculates the transferred heat
of a heat exchanger (= delta
heat).
• Off
• Device on cold side
• Device on warm
side
Device on warm side
Fixed density With order code for "Sensor
version":
• Option "Volume"
or
• Option "Volume high
temperature"
Enter fixed value for medium
density.
Dependency
The unit is taken from the
Density unit parameter.
0.01 to 15 000 kg/m³ 1 000 kg/m³
Fixed density With order code for "Sensor
version":
• Option "Volume"
or
• Option "Volume high
temperature"
Enter fixed value for medium
density.
Dependency
The unit is taken from the
Density unit parameter.
0.01 to 15 000 kg/m³ 5 kg/m³
Fixed temperature – Enter a fixed value for process
temperature.
Dependency
The unit is taken from the
Temperature unit parameter
–200 to 450 °C 20 °C