Proline Prowirl R 200 HART Operation
Endress+Hauser 143
11.6.2 Function scope of the "Reset all totalizers" parameter
Options Description
Cancel No action is executed and the user exits the parameter.
Reset + totalize Resets all totalizers to 0 and restarts the totaling process. This deletes all the flow
values previously totalized.
11.7 Showing data logging
The Extended HistoROM application package must be enabled in the device (order
option) for the Data logging submenu to appear. This contains all the parameters for the
measured value history.
Data logging is also available via:
Plant Asset Management Tool FieldCare →  66.
Function range
A total of 1000 measured values can be stored
4 logging channels
Adjustable logging interval for data logging
Display of the measured value trend for each logging channel in the form of a chart
0
/ ../XXXXXXXX
175.77
40.69 l/h
-100s
A0034352
x-axis: depending on the number of channels selected displays 250 to 1000 measured
values of a process variable.
y-axis: displays the approximate measured value span and constantly adapts this to the
ongoing measurement.
If the length of the logging interval or the assignment of the process variables to the
channels is changed, the content of the data logging is deleted.
Navigation
"Diagnostics" menu → Data logging
Data logging
Assign channel 1
→  144
Assign channel 2
→  144
Assign channel 3
→  144
Assign channel 4
→  145
Logging interval
→  145
Clear logging data
→  145