Commissioning Proline Prowirl R 200 HART
84 Endress+Hauser
10.4.5 Configuring the current output
The Current output wizard guides you systematically through all the parameters that have
to be set for configuring the current output.
Navigation
"Setup" menu → Current output 1 to n
Current output 1 to n
Assign current output 1 to n
→  84
Current span
→  84
4 mA value
→  84
20 mA value
→  85
Fixed current
→  85
Damping output 1 to n
Failure mode
→  85
Failure current
→  85
Parameter overview with brief description
Parameter Prerequisite Description Selection / User
entry
Factory setting
Assign current output Select process variable for
current output.
Off
Volume flow
Corrected volume
flow
Mass flow
Flow velocity
Temperature
Pressure
Calculated
saturated steam
pressure
*
Total mass flow
*
Energy flow
*
Heat flow
difference
*
Volume flow
Current span Select current range for
process value output and
upper/lower level for alarm
signal.
4...20 mA NAMUR
4...20 mA US
4...20 mA
Fixed current
Country-specific:
4...20 mA NAMUR
4...20 mA US
4 mA value One of the following options is
selected in the Current span
parameter (→  84):
4...20 mA NAMUR
4...20 mA US
4...20 mA
Enter 4 mA value. Signed floating-point
number
Country-specific:
0 m³/h
0 ft³/min