Proline Prowirl R 200 HART Electrical connection
Endress+Hauser 43
‣
To remove a cable from the terminal, use a flat-blade screwdriver to push the slot
between the two terminal holes while simultaneously pulling the cable end out of the
terminal.
7.2.2 Connecting the remote version
L
WARNING
Risk of damaging the electronic components!
‣
Connect the sensor and transmitter to the same potential equalization.
‣
Only connect the sensor to a transmitter with the same serial number.
The following procedure (in the action sequence given) is recommended for the remote
version:
1. Mount the sensor and transmitter.
2. Connect the connecting cable for the remote version.
3. Connect the transmitter.
How the connecting cable is connected in the transmitter housing depends on the
measuring device approval and the version of the connecting cable used.
In the following versions, only terminals can be used for connection in the transmitter
housing:
• Certain approvals: Ex nA, Ex ec, Ex tb and Division 1
• Use of reinforced connecting cable
• Order code for "Sensor version; DSC sensor; measuring tube", option DA, DB
In the following versions, an M12 device connector is used for connection in the
transmitter housing:
• All other approvals
• Use of connecting cable (standard)
Terminals are always used to connect the connecting cable in the sensor connection
housing (tightening torques for screws for cable strain relief: 1.2 to 1.7 Nm).
Connecting the sensor connection housing
A0034167
1. Loosen the securing clamp.
2. Unscrew the housing cover.