Proline Prowirl R 200 HART Commissioning
Endress+Hauser 83
Navigation
"Setup" menu → Current input
Current input
External value
→  83
Atmospheric pressure
→  83
Current span
→  83
4 mA value
→  83
20 mA value
→  83
Failure mode
→  83
Failure value
→  83
Parameter overview with brief description
Parameter Prerequisite Description Selection / User
entry
Factory setting
External value With order code for "Sensor
version":
Option "Mass (integrated
temperature measurement)"
or
Option "Mass (integrated
pressure/temperature
measurement)"
Assign variable from external
device to process variable.
For detailed information
on the calculation of the
measured variables with
steam: →  132
Off
Pressure
Gauge pressure
Density
Temperature
2nd temperature
delta heat
Off
Atmospheric pressure In the External value
parameter, the Gauge
pressure option is selected.
Enter atmospheric pressure
value to be used for pressure
correction.
Dependency
The unit is taken from the
Pressure unit parameter
0 to 250 bar 1.01325 bar
Current span Select current range for
process value output and
upper/lower level for alarm
signal.
4...20 mA
4...20 mA NAMUR
4...20 mA US
Country-specific:
4...20 mA NAMUR
4...20 mA US
4 mA value Enter 4 mA value. Signed floating-point
number
0
20 mA value Enter 20 mA value. Signed floating-point
number
Depends on country
and nominal
diameter
Failure mode Define input behavior in alarm
condition.
Alarm
Last valid value
Defined value
Alarm
Failure value In the Failure mode
parameter, the Defined value
option is selected.
Enter value to be used by the
device if input value from
external device is missing.
Signed floating-point
number
0