System integration Proline Prowirl R 200 HART
70 Endress+Hauser
Dynamic variables Measured variables
(HART device variables)
Primary dynamic variable (PV) Volume flow
Secondary dynamic variable (SV) Temperature
Tertiary dynamic variable (TV) Totalizer 1
Quaternary dynamic variable (QV) Totalizer 2
The assignment of the measured variables to the dynamic variables can be modified and
assigned as desired via local operation and the operating tool using the following
parameters:
Expert → Communication → HART output → Output → Assign PV
Expert → Communication → HART output → Output → Assign SV
Expert → Communication → HART output → Output → Assign TV
Expert → Communication → HART output → Output → Assign QV
The following measured variables can be assigned to the dynamic variables:
Measured variables for PV (primary dynamic variable)
Off
Volume flow
Corrected volume flow
Mass flow
Flow velocity
Temperature
Pressure
Calculated saturated steam pressure
Total mass flow
Energy flow
Heat flow difference
Measured variables for SV, TV, QV (secondary, tertiary and quaternary dynamic
variable)
Volume flow
Corrected volume flow
Mass flow
Flow velocity
Temperature
Calculated saturated steam pressure
Total mass flow
Energy flow
Heat flow difference
Condensate mass flow
Reynolds number
Totalizer 1…3
HART input
Density
Pressure
Specific volume
Degrees of superheat
Device variables
The device variables are permanently assigned. A maximum of 8 device variables can be
transmitted:
0 = volume flow
1 = corrected volume flow
2 = Mass flow
3 = flow velocity
4 = temperature
5 = calculated saturated steam pressure