4-3. Function summary of controller external input/output
¢ Controller external input function
Touch panel controller (UTY-DTGZ1)
Dry contact/Apply voltage Dry contact Apply voltage
Function
Emergency stop
●
(Screen icon)
●
(Screen icon)
All on/All off
●
(Screen icon)
●
(Screen icon)
Specifications
Terminal
TM201
(Ch1-K1, K2)
CN201
↕
CN411
TM201
(Ch1-K1, K2)
(Ch2-K1, K2)
CN201
↕
CN411
TM201
(Ch1-K1, K2)
CN201
↕
CN412
TM201
(Ch1-K1, K2)
(Ch2-K1, K2)
CN201
↕
CN412
Signal type Edge
Pulse *
Edge
Pulse *
External
power supply
Allowable
voltage
— DC12 V
Allowable
current
— 10 mA or less
Wire size
0.33 mm
2
(22 AWG), Twisted
Max. cable length 25 m
*: Default setting is Edge signal. If you use Pulse signal, DIP switch 2-2 must be set to “On”.
Central remote controller (UTY-DCGZ)
Dry contact/Apply voltage Dry contact Apply voltage
Function
Emergency stop
●
(Screen icon)
●
(Screen icon)
All on/All off
●
(Screen icon)
●
(Screen icon)
Specifications
Terminal
CN12
(Ch1: Pin 1-2)
CN12
(Ch1: Pin 1-2)
CN13
(Ch2: Pin 1-2)
CN14
(Pin 1-3)
CN14
(Ch1: Pin 1-3)
CN15
(Ch2: Pin 1-3)
Signal type Edge
Pulse
Edge
Pulse
External
power supply
Allowable
voltage
— DC 24 V
Allowable
current
— 5 mA or less
Wire size
0.33 mm
2
(22 AWG), Twisted
Max. cable length 25 m