2-6. Function summary of outdoor unit external input/output
¢ Outdoor unit external input function
Dry contact/ Apply voltage Dry contact DC 12 V
Function
Emergency stop
(20-01)
Low noise mode operation
● *
1
Cooling/Heating priority
Outdoor unit operation peak
control
● *
2
Batch stop
(20-00)
Power usage information from
electricity meter
Specifications
Terminal
CN131
(Pin1-2)
CN132
(Pin1-2)
CN133
(Pin1-2)
CN134
(Pin1-2)
CN135
(Pin1-2)
Signal type Edge Pulse
*
1
:
When using this function, select appropriate level from the following options:
42-00 Low noise level 1 (lower than rated value)
42-01 Low noise level 2 (lower than level 1)
*
2
:
When using this function, select appropriate level from the following options:
30-00 Energy saving level 1 (Stop)
30-01 Energy saving level 2 (Operated at 40% capacity)
30-02 Energy saving level 3 (Operated at 60% capacity)
30-03 Energy saving level 4 (Operated at 80% capacity)
30-04 Energy saving level 5 (Operated at 100% capacity)
NOTES:
For selecting relay, minimum permissible load must be less than 1 mA.
When using Apply voltage, take “+” polarity for Pin 1.
Number inside bracket such as “(20-00)” in the table above indicates function number and set-
ting number.
●: Equipping the function.
¢ Outdoor unit external output function
Dry contact/ Apply voltage Apply voltage Dry contact
Function
Operation status
Error status
Base heater
Specifications
Terminal
CN136
(Pin1-2)
CN137
(Pin1-2)
CN115
(Pin1-3)
Terminal output voltage AC 240 V
External power
supply
Allowable
voltage
DC 12—24 V
Allowable current 30 mA or less 1 A or less
NOTES:
When using Apply voltage, take “+” polarity for Pin 1.
●: Equipping the function.