3-10. BACnet gateway (Software: UTY-ABGXZ1)
It is possible to connect medium to large sized BMS to VRF network system via BACnet, a global
standard for open networks.
A Maximum of 1,600 indoor units with 4 VRF network systems (a maximum of 400 indoor units
and 100 outdoor units for one network system) can be connected to one BACnet gateway.
It is possible to control or monitor VRF network system from BMS via BACnet gateway.
Compatible with BACnet (ANSI/ASHRAE-135-2012) application specific controller (B-ASC).
Compatible with BACnet/IP over Ethernet.
Scheduling function, alarm and event functions, electricity charge apportionment functions as well
as energy saving function are provided in BACnet gateway.
Connection between VRF network system to personal computer is possible via small U10 USB
interface. However, both U10 USB interface and personal computer are locally purchased items.
¢ Accessory
Name and shape Q’ty Application
WHITE-USB-KEY
(Software protection key with software)
1
Includes the software and manuals of tool for BACnet
gateway. Additionally, it works as the software protection
key.
Software protection key to be connected to an USB port on
the PC that the BACnet gateway is installed. BACnet
gateway runs only on a PC with this WHITE-USB-KEY.
¢ Other required devices (Locally purchased)
To install tool for BACnet gateway, personal computer that satisfies the following system require-
ments is necessary.
Personal computer system requirement
Operating
system
Microsoft Windows 7 Home Premium (32-bit or 64-bit) SP1
Microsoft Windows 7 Professional (32-bit or 64-bit) SP1
Microsoft Windows 8.1 (32-bit or 64-bit)
Microsoft Windows 8.1 Pro (32-bit or 64-bit)
Microsoft Windows 10 Home (32-bit or 64-bit)
Microsoft Windows 10 Pro (32-bit or 64-bit)
Supported languages: English, Chinese, French, German, Russian, Spanish, and Polish
CPU Intel Core i3 2 GHz or higher
Memory
2 GB or more (for Windows 7 [32-bit])
4 GB or more (for Windows 7 [64-bit], Windows 8.1, and Windows 10)
HDD 40 GB or more of free space
Display 1,024 × 768 or higher resolution
Interface
Ethernet port (for getting access to the Internet using LAN) or Modem (for getting
access to the Internet using public telephone line)
USB ports (Maximum of 5 ports) (Required only for the server PC that works as VRF
controller)
Maximum of 1 USB ports are required for WHITE-USB-KEY connection
Maximum of 4 USB ports are required for Echelon U10 USB Network Interface
NOTE: Maximum number of required USB ports depends on the applicable
system configuration.
Software Adobe Reader 9.0 or later
Echelon U10 USB Network Interface – TP/FT-10 Channel (Model number: 75010R) (Required for
each VRF network)
3-10. BACnet gateway (Software: UTY-ABGXZ1)