2-3. Pipe size
After referring to cooling capacity table below, select each Pipe size, Separation tube, and Header
from the cooling capacity of outdoor unit and indoor unit connected in the system.
NOTE:
For pipe diameter, material, and wall thickness, refer to "Important items when using refrig-
erant (R410A)" on page 06-14.
¢ Cooling capacity table
Outdoor unit
Ton Model name Cooling capacity (kW)
Maximum
connectable
indoor unit
8
AJ072LELDH
22.4 20
10
AJ090LELDH
28.0 25
12
AJ108LELDH
33.5 30
14
AJ126LELDH
40.0 36
16
AJ144LELDH
45.0 40
18
AJ162LELDH
50.0 42
2-3. Pipe size - (06-19) - 2. Piping design