2-2. 4-way flow cassette type
Model name AUXD18GALH AUXD24GALH
Power supply 230 V ~ 50 Hz
Available voltage range 198—264 V
Capacity
Cooling
kW 5.6 7.1
Btu/h 19,100 24,200
Heating
kW 6.3 8.0
Btu/h 21,500 27,300
Input power W 39 46
Fan
Airflow rate
HIGH
m
3
/h (l/s)
1,150 (319) 1,280 (356)
MED 940 (261) 1,040 (289)
LOW 870 (242)
Type × Q'ty Turbo × 1
Motor output W 80
Sound pressure level*
HIGH
dB (A)
36 38
MED 30 33
LOW 29
Heat exchanger type
Dimensions
(H × W × D)
mm
210 × 2,087 × 13.3
210 × 2,021 × 13.3
Length 2,054
Fin pitch 1.2
Rows × Stages 2 × 10
Face area
m
2
0.42
Pipe type (Material) Grooved H-pin (Copper)
Fin
Type Slit (Aluminum)
Surface treatment Hydrophilic coating
Air filter
Type Anti-mold
Net material PP honeycomb
Enclosure
Material Galvanized sheet iron
Color —
Dimensions
(H × W × D)
Net Main body
mm
246 × 840 × 840
Gross 318 × 960 × 980
Weight
Net
kg
22
Gross 27
Connection pipe diameter
Liquid (Flare)
mm (in)
Ø 9.52 (Ø 3/8)
Gas (Flare) Ø 15.88 (Ø 5/8)
Drain hose
VP25
I.D.: Ø 25 (1); O.D.: Ø 32 (1-1/4)
Cassette grille
(Option)
Model name
UTG-UGA-W
Color
White
Approximate color of Munsell N9.25/
Dimensions
(H × W × D)
Net
mm
50 × 950 × 950
Gross 115 × 1,020 × 1,000
Weight
Net
kg
5.5
Gross 8.5
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Pipe length: 7.5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
2-2. 4-way flow cassette type
- (04-6) - 2. Specifications
INDOOR
UNITS
INDOOR