2-2. Piping limitation
For proper system operation, keep all the piping limitation mentioned here.
CAUTION
Allowable height difference:
If the height difference between indoor unit and outdoor unit is larger than the allowable value:
The pressure loss will be larger. → Insufficient cooling and heating
The refrigerant in liquid pipe will flush. → Refrigerant flow noise generate at indoor unit
The refrigerant oil will not return.
→ Insufficient refrigerant oil resulting in compressor damage
If the height difference between indoor units is larger than the allowable value:
The refrigerant flow balance will be poor. → Insufficient cooling and heating (poor balance)
Refrigerant oil will collect in the piping or non-operating indoor units.
→ Insufficient refrigerant oil resulting in compressor damage
Piping length:
If the piping length is longer than prescribed:
The pressure loss will be larger. → Insufficient cooling and heating
Too much refrigerant will be charged. → Liquid backs up resulting in compressor damage
The refrigerant oil will not return. → Insufficient refrigerant oil resulting in compressor damage
Pipe size:
If the pipe size is larger than designated size:
The refrigerant flow velocity will drop. Refrigerant oil will not return to the outdoor unit.
→ Insufficient refrigerant oil resulting in compressor damage
The refrigerant in liquid pipe will flush easily. → Insufficient cooling and heating
If the pipe size is smaller than designated size:
The refrigerant circulation volume will drop. → Insufficient cooling and heating
The pressure loss will be larger. → Insufficient cooling and heating
Indoor unit connected capacity:
If the indoor unit connected capacity is larger than the system capacity:
Insufficient system performance. → Insufficient cooling and heating
When heating, refrigerant will collect in non-operating indoor units resulting in an insufficient
refrigerant circulation volume. → Insufficient cooling and heating
The refrigerant oil will not return. → Compressor damage
If the indoor unit connected capacity is too small compared to the system capacity:
The liquid return will be too great. → Compressor damage
The refrigerant will concentrate in the outdoor unit.
→ Continuous operation will become difficult due to the outdoor unit stopping due to high
head pressure. Also, excessive noise will be generated by the refrigerant flow when in heat-
ing mode.