2-19. Network convertor (UTY-VTGX, UTY-VTGXV)
¢ Switch location
Set the rotary switches (SET1) and DIP switches (SET2, SET3) on the network convertor PCB.
SET2
SET3
3WIRE
2WIRE
SET1
¢ Rotary switch setting
SET1: Refrigerant circuit address setting
Refrigerant circuit
address
(Example)
Rotary switch setting
SET1 (x10)
(10 digit)
SET1 (x1)
(1 digit)
01
0 1
99
9 9
NOTES:
Setting range: 00 to 99 (Arbitrary numbers can be set.)
When connecting the Network converter for single split air conditioner, set up the number so
that the refrigerant circuit address number of the outdoor unit and indoor unit does not over-
lap. The sum total of the refrigerant circuit address of Network converter for single split air
conditioner, outdoor unit and the indoor unit is a maximum of 100.
2-19. Network convertor (UTY-VTGX, UTY-VTGXV)
- (07-129) - 2. Function settings
FUNCTION
SETTINGS
FUNCTION
SETTINGS