3. Press the “
” button. If there is no problem, return to Menu 2-F1 items selection screen. In the
case of settings at initial booting, display Monitor mode screen.
If there is 0 or more than 2 Master units, the number will be displayed.
• If “Master” is 0, press the “
” button to return to the Menu 2-F1 item selection screen.
• If “Master” is more than 2, press the “
” button to return to the screen in previous step.
• To suspend the settings part way through and return to the Menu 2-F1 item screen, press
FAN “ ” button.
NOTE:
Set only one master remote controller.
¢ Indoor unit address verification
1. Select the “10” in Menu 2-F2 Settings. Then press the “
” button.
2. Display the smallest 2-wire remote controller address of indoor unit (system number and unit
number) of the remote controller group. This address displayed can be switched by the TEMP.
“
” or TEMP. “ ” button. If an indoor unit other than VRF is connected, “-” is displayed.
Press the “
” button to display the refrigerant system address and indoor unit address.
(a) System number (002: Indoor unit)
(b) Unit number (01 to 32)
(c) Refrigerant system address (00 to 99)
(d) Indoor unit address (00 to 63)
3.
Press the FAN “ ” button to return to the Menu 2-F2 item selection screen.
2-18. Simple remote controller (UTY-RSR
, UTY-RHR)
- (07-128) - 2. Function settings
FUNCTION
SETTINGS
FUNCTION
SETTINGS