2-14. Ceiling type
Model name
ABA030GTEH ABA036GTEH ABA045GTEH ABA054GTEH
Power supply 230 V ~ 50 Hz
Available voltage range 198—264 V
Capacity
Cooling
kW 9.0 11.2 12.5 14.0
Btu/h 30,700 38,200 42,700 47,800
Heating
kW 10.0 12.5 14.0 16.0
Btu/h 34,100 42,700 47,800 54,600
Input power W 66 85 131 180
Fan
Airflow rate
HIGH
m
3
/h (l/s)
1,630 (453) 1,690 (469) 2,010 (558) 2,270 (631)
MED—HIGH 1,520 (422) 1,560 (433) 1,840 (511) 2,070 (575)
MED 1,420 (394) 1,450 (403) 1,690 (469) 1,860 (517)
MED—LOW 1,320 (367) 1,360 (378) 1,530 (425) 1,660 (461)
LOW 1,220 (339) 1,270 (353) 1,380 (383) 1,470 (408)
QUIET 1,140(317) 1,170(325) 1,230(342) 1,280(356)
Type × Q'ty Sirocco × 4
Motor output W 130
Sound pressure level*
HIGH
dB (A)
42 45 48 51
MED—HIGH 40 41 46 49
MED 39 45 46
MED—LOW 37 38 41 43
LOW 35 36 38 40
QUIET 33 34 35 36
Heat exchanger type
Dimensions (H × W × D)
mm
252 × 1,350 ×39.9
Main: 252 × 1,350 ×39.9
Sub: 168 × 1,350 × 13.3
Length 1,350
Fin pitch 1.45
Rows × Stages 3 × 12
Main: 3 × 12
Sub: 1 × 8
Face area
m
2
0.34
Pipe type (Material) Grooved H-pin (Copper)
Fin
Type (Material) Slit (Aluminum)
Surface treatment Hydrophilic coating
Air filter Net material PP monofilament net
Enclosure
Material Plastic
Color
White
Approximate color of Munsell N9.25/
Dimensions
(H × W × D)
Net
mm
240 × 1,660 × 700
Gross 318 × 1,800 × 790
Weight
Net
kg
46 48
Gross 59 61
Connection pipe diameter
Liquid (Flare)
mm (in)
Ø 9.52 (Ø 3/8)
Gas (Flare) Ø 15.88 (Ø 5/8)
Drain hose
VP25
I.D.: Ø 25 (1); O.D.: Ø 32 (1-1/4)
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Pipe length: 7.5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
2-14. Ceiling type
- (04-28) - 2. Specifications
INDOOR
UNITS
INDOOR
UNITS