7. Operation range
7-1. Outdoor unit
Operation mode
AJ072LELDH
AJ090LELDH
AJ108LELDH
AJ126LELDH
AJ144LELDH
AJ162LELDH
Cooling/Dry
-15 to 46 °CDB *
1
-5 to 46 °CDB *
1
*
2
Heating -20 to 21 °CDB
*1: When installation position of the outdoor unit is lower than the indoor unit, the operation tempera-
ture range is -5 to 46 °CDB.
*2: The cooling operation range of -15 to 46 °CDB is allowed only when all of the connected indoor
units are higher than capacity of 5.6 kW.
7-2. Indoor unit
Operation mode Operation range
Cooling/Dry
18 to 32 °CDB
R.H. 80% or less
Heating 10 to 30 °CDB
R.H.: Relative humidity
7-1. Outdoor unit - (03-26) - 7. Operation range