2-7. Low static pressure duct (Slim duct)/Slim concealed floor
type
Model name ARXD007GLEH ARXD009GLEH ARXD012GLEH
Power supply 230 V ~ 50 Hz
Available voltage range 198—264 V
Capacity
Cooling
kW 2.2 2.8 3.6
Btu/h 7,500 9,600 12,300
Heating
kW 2.8 3.2 4.0
Btu/h 9,600 10,900 13,600
Input power W 44 50 54
Static pressure range Pa 0 to 90
Standard static pressure Pa 25
Fan
Airflow rate
HIGH
m
3
/h (l/s)
550 (153) 600 (167) 600 (167)
MED—HIGH 480 (133) 510 (142) 530 (147)
MED 440 (122) 460 (128) 490 (136)
MED—LOW 410 (114) 420 (117) 450 (125)
LOW 370 (103) 370 (103) 410 (114)
QUIET 320 (89) 320 (89) 340 (94)
Type × Q'ty Sirocco × 2
Motor output W 80 81
Sound pressure level*
HIGH
dB (A)
28 29 30
MED—HIGH 26 27 28
MED 25 25 27
MED—LOW 24 24 26
LOW 22 22 24
QUIET 21 21 22
Heat exchanger type
Dimensions (H × W × D)
mm
294 × 500 ×26.6 294 × 500 ×39.9
Length 500
Fin pitch 1.3
Rows × Stages 2 × 14 3 × 14
Face area
m
2
0.15
Pipe type (Material) Grooved H-pin (Copper)
Fin
Type (Material) Slit (Aluminum)
Surface treatment Hydrophilic coating
Air filter Net material PP honeycomb
Enclosure
Material Galvanized sheet iron
Color
Dimensions
(H × W × D)
Net
mm
198 × 700 × 620
Gross 270 × 935 × 770
Weight
Net
kg
17 18
Gross 21 23
Connection pipe diameter
Liquid (Flare)
mm (in)
Ø 6.35 (Ø 1/4)
Gas (Flare) Ø 9.52 (Ø 3/8) Ø 12.70 (Ø 1/2)
Drain hose
VP25
I.D.: Ø 25 (1); O.D.: Ø 32 (1-1/4)
NOTES:
Specifications are based on the following conditions:
Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
Pipe length: 7.5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
Protective function might work when using it outside the operation range.
*: Sound pressure level:
Measured values in manufacturer’s anechoic chamber.
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
2-7. Low static pressure duct (Slim duct)/Slim concealed floor type
- (04-17) - 2. Specifications