Model name ARXK014GLGH ARXK018GLGH ARXK024GLGH
Power supply 230 V ~ 50 Hz
Available voltage range 198—264 V
Capacity
Cooling
kW 4.5 5.6 7.1
Btu/h 15,400 19,100 24,200
Heating
kW 5.0 6.3 8.0
Btu/h 17,100 21,500 27,300
Input power W 66 73 80
Static pressure range Pa 0 to 50
Standard static pressure Pa 15
Fan
Airflow rate
HIGH
m
3
/h (l/s)
760 (211) 930 (258) 1,160 (322)
MED—HIGH 660 (183) 840 (233) 1,060 (294)
MED 560 (156) 740 (206) 960 (267)
MED—LOW 490 (136) 640 (178) 860 (239)
LOW 410 (114) 540 (150) 750 (208)
QUIET 340 (94) 470 (131) 610 (169)
Type × Q'ty Sirocco × 2 Sirocco × 3 Sirocco × 4
Motor output W 80 81
Sound pressure level*
HIGH
dB (A)
34 33 32
MED—HIGH 31 30
MED 28
MED—LOW 26 27
LOW 24 25
QUIET 22
Heat exchanger type
Dimensions (H × W × D)
mm
336 × 490 × 26.6 336 × 690 × 26.6 336 × 890 × 26.6
Length 490 690 890
Fin pitch 1.3
Rows × Stages 2 × 16
Face area
m
2
0.16 0.23 0.30
Pipe type (Material) Grooved H-pin (Copper)
Fin
Type Slit (Aluminum)
Surface treatment Hydrophilic coating
Air filter Net material PP honeycomb
Enclosure
Material Galvanized sheet iron
Color —
Dimensions
(H × W × D)
Net
mm
198 × 700 × 450 198 × 900 × 450 198 × 1,100 × 450
Gross 250 × 930 × 580 250 × 1,130 × 580 250 × 1,330 × 580
Weight
Net
kg
GLGH: 16.0
GLFH: 15.5
GLGH: 19.0
GLFH: 18.5
GLGH: 22.5
GLFH: 22.0
Gross
GLGH: 19.5
GLFH: 18.0
GLGH: 23.0
GLFH: 22.0
GLGH: 26.5
GLFH: 25.0
Connection pipe diameter
Liquid (Flare)
mm (in)
Ø 6.35 (Ø 1/4) Ø 9.52 (Ø 3/8)
Gas (Flare) Ø 12.70 (Ø 1/2) Ø 15.88 (Ø 5/8)
Drain hose
VP25
I.D.: Ø 25 (1); O.D.: Ø 32 (1-1/4)
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Pipe length: 7.5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
2-6. Low static pressure duct (Mini duct) type
- (04-16) - 2. Specifications
INDOOR
UNITS
INDOOR
UNITS