2. Specifications
2-1. Compact cassette type
Model name AUXB004GLEH AUXB007GLEH AUXB009GLEH
Power supply 230 V ~ 50 Hz
Available voltage range 198—264 V
Capacity
Cooling
kW 1.1 2.2 2.8
Btu/h 3,800 7,500 9,600
Heating
kW 1.3 2.8 3.2
Btu/h 4,400 9,600 10,900
Input power W 23 25
Fan
Airflow rate
HIGH
m
3
/h (l/s)
530/530*
1
(147/147)
540 (150) 550 (153)
MED—HIGH
490/480*
1
(136/133)
500 (139) 520 (144)
MED
450/430*
1
(125/119)
460 (128) 480 (133)
MED—LOW
420/380*
1
(117/106)
420 (117) 440 (122)
LOW
390/340*
1
(108/94)
390 (108) 400 (111)
QUIET
350/300*
1
(97/83)
350 (97)
Type × Q'ty Turbo × 1
Motor output W 54
Sound pressure level*
2
HIGH
dB (A)
34/34*
1
34 35
MED—HIGH
32/31*
1
32 33
MED
30/29*
1
30 31
MED—LOW
28/26*
1
28 29
LOW
27/24*
1
27
QUIET
25/21*
1
25
Heat exchanger type
Dimensions
(H × W × D)
mm
210 × 1,310 × 13.3
210 × 1,250 × 13.3
Length 1,280
Fin pitch 1.2
Rows × Stages 2 × 10
Face area
m
2
0.27
Pipe type (Material) Grooved H-pin (Copper)
Fin
Type (Material) Slit (Aluminum)
Surface treatment Hydrophilic coating
Air filter Net material PP honeycomb
Enclosure
Material Galvanized sheet iron
Color
Dimensions
(H × W × D)
Net Main body
mm
245 × 570 × 570
Gross 265 × 730 × 625
Weight
Net
kg
14.5 15
Gross 18
Connection pipe diameter
Liquid (Flare)
mm (in)
Ø 6.35 (Ø 1/4)
Gas (Flare) Ø 9.52 (Ø 3/8)
Drain hose
VP25
I.D.: Ø 25 (1); O.D.: Ø 32 (1-1/4)
Cassette grille
(Grid type: Option)
Model name
UTG-UFE-W
Color
White
Approximate color of Munsell 9PB 9.1/0.2
Dimensions
(H × W × D)
Net
mm
50 × 620 × 620
Gross 120 × 765 × 755
Weight
Net
kg
2.3
Gross 4.5
Cassette grille
(Standard type: Option)
Model name
UTG-UFC-W
Color
White
Approximate color of Munsell N9.25/
Dimensions
(H × W × D)
Net
mm
50 × 700 × 700
Gross 120 × 765 × 755
Weight
Net
kg
2.6
Gross 4.5
NOTES:
Specifications are based on the following conditions:
Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
Pipe length: 7.5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
Protective function might work when using it outside the operation range.
*1: This value is “Cooling operation/Heating operation”.
*2: Sound pressure level:
Measured values in manufacturer’s anechoic chamber.
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.