10. Safety devices
10-1. Compact cassette type
Model Fuse
Fan motor thermal protector
Terminal
thermal fuse
Float
switch
Active Reset
AUXB004GLEH
250 V
3.15 A
125 ±10°C
Fan motor stop
120 ±10°C
Fan motor restart
— ○
AUXB007GLEH
140 ±20°C
Fan motor stop
110 ±20°C
Fan motor restart
AUXB009GLEH
AUXB012GLEH
AUXB014GLEH
AUXB018GLEH
AUXB024GLEH
10-2. 4-way flow cassette type
Model Fuse
Fan motor thermal protector
Terminal
thermal fuse
Float
switch
Active Reset
AUXD18GALH
250 V
3.15 A
110
+15
-10
°C
Fan motor stop
105
+15
-10
°C
Fan motor Restart
— ○
AUXD24GALH
AUXA30GALH
AUXA34GALH
AUXA36GALH
AUXA45GALH
AUXA54GALH
10-3. Circular flow cassette type
Model Fuse
Fan motor thermal protector
Terminal
thermal fuse
Float
switch
Active Reset
AUXM018GLEH
250 V
3.15 A
125 ±10°C
Fan motor stop
120 ±10°C
Fan motor Restart
— ○
AUXM024GLEH
AUXM030GLEH
AUXK018GLEH
AUXK024GLEH
AUXK030GLEH
AUXK034GLEH
AUXK036GLEH
AUXK045GLEH
AUXK054GLEH
10-4. 3D flow cassette type
Model Fuse
Fan motor thermal protector
Terminal
thermal fuse
Float
switch
Active Reset
AUXS018GLEH
250 V
3.15 A
135 ±15°C
Fan motor stop
115 ±15°C
Fan motor Restart
— ○
AUXS024GLEH
10-1. Compact cassette type - (04-296) - 10. Safety devices
INDOOR
UNITS
INDOOR