5-2. Indoor unit
¢
General rules of drain piping
Install the drain pipe with downward slope (1/100 or more) and so there are no rises in the pipe.
Use general hard polyvinyl chloride pipe (VP25Ø3/4 [I.D.], Ø1-1/6 [O.D.]) and connect it with adhe-
sive (polyvinyl chloride) so that there is no leakage.
Support the drain pipe with supports each 1.5 to 2.0 m.
Do not install any air vents or traps.
Always insulate the drain pipe to prevent condensation.
When connecting the drain hose to the indoor unit, use the accessory band. (Except wall mounted
type)
¢
Compact cassette type
300 mm or less
Max. 700 mm
Attached band
Drain hose
(accessory)
Downward gradient
1/100 to 1/50
Horizontal
or upward
gradient
VP25
(Locally purchased)
1.5 m to 2.0 m
Downward gradient
1/100 to 1/50
Hanging fitting
Air bleeding
Rise
Trap
Ï
Ï
Ï
Prohibited
Drain lift-up pipe restrictions:
Lift-up height ≤ 700 mm (from ceiling)
Drain hose (pipe) length ≤ 300 mm (between indoor unit and lift-up pipe)
Water leakage may result from a failure to adhere to the restrictions above.
5-2. Indoor unit
- (06-66) - 5. Drain connection