2-5. Additional charge calculation
NOTES:
The outdoor unit is charged refrigerant at the factory.
Additional refrigerant required to be charged on site depending on pipe length and outdoor unit
model.
The additional refrigerant charge amount is calculated according to the following formula.
Round up the calculated result to two decimal places.
¢ Calculation formula
Calculation of additional amount for pipe length (A)
Diameter of liquid pipe a: Additional amount for pipe length
mm kg/m
Ø6.35 0.021
Ø9.52 0.058
Ø12.70 0.114
A =
Total length of
Ø12.70 mm
liquid pipe
a:
× 0.114 kg/m
+
Total length of
Ø9.52 mm
liquid pipe
a:
× 0.058 kg/m
+
m
m
kg kg
Total length of
Ø6.35 mm
liquid pipe
a:
× 0.021 kg/m
=
Total
m
kg
kg
A =
kg
Round up A to 2 decimal place.
Factory charge amount (B)
Model name HP
b: Factory charged amount
kg
AJ072LELDH
8 7.0
AJ090LELDH
10 7.5
AJ108LELDH
12 7.5
AJ126LELDH
14 11.0
AJ144LELDH
16 11.0
AJ162LELDH
18 11.8
B =
b: Outdoor unit
Factory charge amount
kg
2-5. Additional charge calculation - (06-27) - 2. Piping design