1-5. Automatic address setting
The addresses of signal amplifiers and indoor units can be set automatically.
CAUTION
• Mind the following items when performing automatic address setting.
– The controller cannot be used.
– Automatic address setting may take about 30 minutes.
– Emergency stop signal is not accepted.
• When setting both addresses of Signal amplifiers and indoor units automatically, be sure to al-
ways set the addresses of signal amplifiers first.
¢ Automatic address setting method
Automatic address setting needs to be performed by following steps mentioned below in order.
<Step 1>
Manual setting of outdoor unit
Refer to the set up procedures in following sections:
• "Manual address setting method" on page 07-9
• "Terminal resistor setting" on page 07-63
↓
<Step 2>
Turning power on of all units
↓
<Step 3>
Automatic address setting of Signal
amplifier
Refer to the set up procedure in following section:
"Automatic address setting of signal amplifier" on page 07-
57
↓
<Step 4>
Automatic address setting of indoor
unit
Refer to the set up procedure in following section:
"Automatic address setting of indoor unit" on page 07-59
1-5. Automatic address setting - (07-55) - 1. System settings