4-2. Central remote controller (UTY-DCGZ)
External input and output functions and related components are as follows:
External input External output Input select Connector
External connect kit
(Optional parts)
Control input
Dry contact CN12, CN13 UTY-XWZXZ7
Apply voltage CN14, CN15 UTY-XWZXZ8
Operation status
CN18 UTY-XWZXZA
Error status
RELATED LINKS
"External input" on page 08-32
"External output" on page 08-36
"Optional parts" on page 08-37
"Function summary of controller external input/output" on page 08-38
¢ External input
This function performs “Emergency stop” or “All On / All Off” by using the signal to be input externally
at external input terminals.
Input select
Use either one of Apply voltage terminal or Dry contact terminal according to the application. (Both
types of terminals cannot be used simultaneously.)
CN12 (CH1) and CN13 (CH2): Dry contact terminal
When a power supply is unnecessary at the input device you want to connect, use the Dry contact
terminal CN12 (Ch1) and CN13 (Ch2).
PCB
CN13 (Ch2, Black)
CN12 (Ch1, White)
*
Connected unit
*: Short circuit detection resistance (R
ON
): ≤ 500 Ω
Open circuit detection resistance (R
OFF
): ≥ 100 kΩ
A twisted pair cable 0.33 mm
2
(22 AWG) should be used. (Maximum cable length: 25 m)
Input method Terminal Input signal Operation
Edge CN12 (Ch1)
Low → High
“Emergency Stop”
or “All on”
High → Low
“Emergency Stop” reset
or “All Off”
Pulse
CN12 (Ch1) Low → High
“Emergency Stop”
or “All on”
CN13 (Ch2) Low → High
“Emergency Stop” reset
or “All Off”
4-2. Central remote controller (UTY-DCGZ) - (08-32) - 4. Controller
EXTERNAL INPUT
AND OUTPUT
EXTERNAL INPUT
AND OUTPUT