CN14 (Ch1) and CN15 (Ch2): Apply voltage terminal
When a power supply must be provided at the input device you want to connect, connect to CN14
(Ch1) and CN15 (Ch2).
*3
*2
*1
*3
PCB
CN14 (Ch1, White)
Power supply
DC 24 V
CN15 (Ch2, Black)
*
1
:
Make the power supply DC 24 V. Select a power supply capacity with an ample sur-
plus for the connected load.
*
2
:
Do not impress a voltage exceeding 24 V across pin 1-3.
*
3
:
The allowable current is DC 5 mA or less. (Recommended: DC 5 mA)
Provide a load resistance such that the current becomes DC 5 mA or less.
A twisted pair cable 0.33 mm
2
(22 AWG) should be used. (Maximum cable length: 25 m)
Input method Terminal Input signal Operation
Edge CN14 (Ch1)
Low → High
“Emergency Stop”
or “All on”
High → Low
“Emergency Stop” reset
or “All Off”
Pulse
CN14 (Ch1) Low → High
“Emergency Stop”
or “All on”
CN15 (Ch2) Low → High
“Emergency Stop” reset
or “All Off”
4-2. Central remote controller (UTY-DCGZ) - (08-33) - 4. Controller
EXTERNAL INPUT
AND OUTPUT
EXTERNAL INPUT
AND OUTPUT