10-13. Floor/Ceiling type
Model Fuse
Fan motor thermal protector
Terminal
thermal fuse
Float
switch
Active Reset
ABA012GTEH
250 V
3.15 A
135 ±15°C
Fan motor stop
115 ±15°C
Fan motor restart
— —
ABA014GTEH
ABA018GTEH
ABA024GTEH
10-14. Ceiling type
Model Fuse
Fan motor thermal protector
Terminal
thermal fuse
Float
switch
Active Reset
ABA030GTEH
250 V
5 A
135 ±15°C
Fan motor stop
115 ±15°C
Fan motor restart
— ▲*
ABA036GTEH
ABA045GTEH
ABA054GTEH
*: Including in Drain pump unit (Optional parts)
10-15. Wall mounted type
Model Fuse
Fan motor thermal protector
Terminal
thermal fuse
Float
switch
Active Reset
ASA004GCGH
250 V
3.15 A
160 ±25°C
Fan motor stop
110 ±25°C
Fan motor restart
—
—
ASA007GCGH
ASA009GCGH
ASA012GCGH
ASA014GCGH
ASA018GCEH
120 ±15°C
Fan motor stop
—
Active at
102°C
ASA024GCEH
ASA030GTEH
150 ±15°C
Fan motor stop
Less than 135°C
Fan motor restart
—
ASA034GTEH
10-16. Wall mounted type (EEV external model)
Model Fuse
Fan motor thermal protector
Terminal
thermal fuse
Float
switch
Active Reset
ASE004GCEH
250 V
3.15 A
160 ±25°C
Fan motor stop
110 ±25°C
Fan motor restart
— —
ASE007GCEH
ASE009GCEH
ASE012GCEH
ASE014GCEH
10-13. Floor/Ceiling type - (04-299) - 10. Safety devices