10-9. Medium static pressure duct type
Model Fuse
Fan motor thermal protector
Terminal
thermal fuse
Float
switch
Active Reset
ARXA024GLEH
250 V
5 A
135 ±15°C
Fan motor stop
115 ±15°C
Fan motor Restart
— ▲*
ARXA030GLEH
115 ±15°C
Fan motor stop
70°C or less
Fan motor Restart
ARXA036GLEH
ARXA045GLEH
*: Including in Drain pump unit (Optional parts)
10-10. High static pressure duct type
Model Fuse
Fan motor thermal protector
Terminal
thermal fuse
Float
switch
Active Reset
ARXC036GTEH
250 V
3.15 A
115 ±15°C
Fan motor stop
70°C or less
Fan motor restart
— —
ARXC045GTEH 250 V, 3.15 A
250 V, 10 A*
145 ±5°C
Fan motor stop
—
ARXC060GTEH
ARXC072GTEH
250 V, 3.15 A
250 V, 20 A*
100
+15
-10
°C
Fan motor stop
95
+15
-10
°C
Fan motor restart
ARXC090GTEH
ARXC096GTEH
*: Fuse for fan motor
10-11. Compact floor type
Model Fuse
Fan motor thermal protector
Terminal
thermal fuse
Float
switch
Active Reset
AGA004GCGH
250 V
3.15 A
150 ±15°C
Fan motor stop
120 ±15°C
Fan motor restart
— —
AGA007GCGH
AGA009GCGH
AGA012GCGH
AGA014GCGH
10-12. Compact floor type (EEV external model)
Model Fuse
Fan motor thermal protector
Terminal
thermal fuse
Float
switch
Active Reset
AGE004GCEH
250 V
3.15 A
150 ±15°C
Fan motor stop
120 ±15°C
Fan motor restart
— —
AGE007GCEH
AGE009GCEH
AGE012GCEH
AGE014GCEH
10-9. Medium static pressure duct type - (04-298) - 10. Safety devices