2-20. Network convertor (UTY-VGGXZ1)
¢ Switch location
Set the rotary switches (SW110, SW111) on the network convertor PCB.
SW111SW110
¢ Rotary switch setting
Convertor address setting for Group remote controller
Convertor address
(Example)
Rotary switch setting
SW110
(10 digit)
SW111
(1 digit)
01
0 1
15
1 5
NOTES:
Setting range: 00 to 15 (Arbitrary numbers can be set.)
The sum total of the Touch panel controller, Central remote controller, Network converter
for Group remote controller, Modbus converter, and Network converter for LonWorks is a
maximum of 16.
For Touch panel controller, Central remote controller, Network converter for Group re-
mote controller, Modbus converter, and Network converter for LonWorks connected in
same VRF network system, set an exclusive address on each device.