2-4. 3D flow cassette type
Model name AUXS018GLEH AUXS024GLEH
Power supply 230 V ~ 50 Hz
Available voltage range 198—264 V
Capacity
Cooling
kW 5.60 7.10
Btu/h 19,100 24,200
Heating
kW 6.30 8.00
Btu/h 21,500 27,300
Input power*
1
W 20/28 34/43
Fan
Airflow rate*
1
HIGH
m
3
/h (l/s)
750/870
(208/242)
950/1,040
(264/289)
MED—HIGH
710/830
(197/231)
890/990
(247/275)
MED
690/780
(192/217)
860/930
(239/258)
MED—LOW
660/740
(183/206)
810/880
(225/244)
LOW
630/700
(175/194)
770/840
(214/233)
QUIET
540/540
(150/150)
540/540
(150/150)
Type × Q'ty Sirocco × 4
Motor output W 80
Sound pressure level*
1
*
2
HIGH
dB (A)
38/41 43/46
MED—HIGH 36/40 42/45
MED 35/39 41/43
MED—LOW 35/37 40/42
LOW 33/36 38/40
QUIET 29/29 29/29
Heat exchanger type
Dimensions (H × W × D)
mm
160 × 1,045 × 60
Length 1,045
Fin pitch 1.20
Rows × Stages 6 × 10
Face area
m
2
0.33
Pipe type (Material) Grooved H-pin (Copper)
Fin
Type (Material) Slit (Aluminum)
Surface treatment Hydrophilic coating
Air filter Net material PP honeycomb
Enclosure
Material Galvanized sheet iron
Color —
Dimensions
(H × W × D)
Net Main body
mm
200 × 1,240 × 500
Gross 305 × 1,530 × 695
Weight
Net
kg
25.0
Gross 34.0
Connection pipe diameter
Liquid (Flare)
mm (in)
Ø 6.35 (Ø 1/4) Ø 9.52 (Ø 3/8)
Gas (Flare) Ø 12.70 (Ø 1/2) Ø 15.88 (Ø 5/8)
Drain hose
VP25
I.D.: Ø 25 (1); O.D.: Ø 32 (1-1/4)
Cassette grille
(Option)
Model name
UTG-USA-W
Color
White
Approximate color of Munsell 10N08
Dimensions
(H × W × D)
Net
mm
85 × 1,350 × 580
Gross 205 × 1,440 × 703
Weight
Net
kg
11.5
Gross 18.0
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Pipe length: 7.5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *1: This value is “Cooling operation/Heating operation”.
• *2: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
2-4. 3D flow cassette type
- (04-12) - 2. Specifications
INDOOR