2. Specifications
2-1. Stand-alone
Nominal system capacity HP 8 10 12
Model name
AJ072LELDH AJ090LELDH AJ108LELDH
Power supply 3N 400 V ~ 50 Hz
Available voltage range 342—456 V
Capacity
Cooling Rated
kW 22.4 28.0 33.5
Btu/h 76,400 95,500 114,300
Heating
Rated (Nominal)
kW 22.4 28.0 33.5
Btu/h 76,400 95,500 114,300
Maximum
kW 25.0 31.5 37.5
Btu/h 85,300 107,400 127,900
Input power
Cooling Rated
kW
6.30 8.59 10.42
Heating
Rated (Nominal) 4.65 6.61 8.18
Maximum 5.45 8.29 10.25
Current
Cooling Rated
A
10.8 13.9 16.5
Heating Rated (Nominal) 8.4 11.2 13.3
Power factor
Cooling
%
84 89 91
Heating 80 85 89
EER Cooling
W/W
3.56 3.26 3.22
COP Heating
Rated (Nominal) 4.82 4.24 4.10
Maximum 4.56 3.80 3.66
Fan
Airflow rate
Cooling
HIGH
m
3
/h (l/s)
8,400 (2,334) 9,000 (2,500)
11,000 (3,056)
Heating 12,100 (3,361)
External static pressure (Max.) Pa 30 40
Type × Q'ty Propeller fan × 2
Motor
Type × Q'ty DC motor × 2
Motor output W 111 200
Sound pressure level*
Cooling
dB (A)
52 54 59
Heating 54 57 62
Sound power level
Cooling
dB (A)
66 69 73
Heating 66 70 75
Heat exchanger type
Length
mm
1,293
Fin pitch 1.45
Rows × Stages 2 × 66 2.6 × 66
Face area
m
2
1.79
Pipe type (Material) Grooved H-pin (Copper)
Fin
Type Corrugate (Aluminum)
Surface treatment Corrosion resistance (Blue fin)
Compressor
Type × Q'ty Scroll (inv) × 1
Displacement
cm
3
66.2
Motor output kW 4.7
Crankcase heater W 35
Refrigerant
Type (Global Warming Potential) R410A (2088)
Charge kg 7.0 7.5
Refrigerant oil
Type FVC68D
Amount
cm
3
2,300
Enclosure
Material Painted galvanized steel
Color
Beige
Approximate color of Munsell 10YR 7.5/1.0NN
Dimensions
(H × W × D)
Net
mm
1,428 × 1,080 × 480
Gross 1,557 × 1,174 × 600
Weight
Net
kg
170 177 178
Gross 188 195 197
Connection pipe
Pipe diameter
Liquid
mm (in)
Ø 9.52 (Ø 3/8) Ø 12.70 (Ø 1/2)
Suction gas Ø 19.05 (Ø 3/4) Ø 22.22 (Ø 7/8) Ø 28.58 (Ø 1-1/8)
Method
Liquid Brazing
Suction gas Brazing
Between outdoor unit and the far-
thest indoor unit
m
120
Total pipe length 400
Max. height difference 50/40 (Outdoor unit: Higher/Lower)
Operation temperature range
Cooling
°CDB
-15 to 46
Heating -20 to 21
Defrost method Reversed cycle
Compressor capacity control (Steps/Range) 106 steps/15 to 120 rps
Connectable indoor units number
Maximum 20 25 30
Minimum 1
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Pipe length: 7.5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
• This data is based on following standard: EN14511, EN12102.
• Protective function might work when using it outside the operation range.
• *: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.