2-8. Low static pressure duct type (High efficiency)
Model name ARXP018GLFH ARXP030GLFH
Power supply 220—240 V ~ 50 Hz
Available voltage range 198—264 V
Capacity
Cooling
kW 5.6 9.0
Btu/h 19,100 30,700
Heating
kW 6.3 10.0
Btu/h 21,500 34,100
Input power W 128 228
Static pressure range Pa 0 to 80
Standard static pressure Pa 40 50
Fan
Airflow rate
HIGH
m
3
/h (l/s)
1,540/1,440*
1
(428/400) 1,940/1,660*
1
(539/461)
MED—HIGH
1,460/1,380*
1
(406/383) 1,810/1,580*
1
(503/439)
MED
1,380/1,320*
1
(383/367) 1,680/1,510*
1
(467/419)
MED—LOW
1,300/1260*
1
(361/350) 1,550/1,440*
1
(431/400)
LOW
1,220/1,200*
1
(339/333) 1,420/1,370*
1
(394/381)
QUIET
1,150/1,150*
1
(319/319) 1,300/1,300*
1
(361/361)
Type × Q'ty Sirocco × 2
Motor output W 197
Sound pressure level*
HIGH
dB (A)
35/34*
1
39/36*
1
MED—HIGH
34/32*
1
38/35*
1
MED
32/31*
1
36/34*
1
MED—LOW
31/30*
1
34/33*
1
LOW
29/29*
1
32/31*
1
QUIET
28/28*
1
30/30*
1
Heat exchanger type
Dimensions (H × W × D) mm 294 × 1,000 × 53.2
Length
mm
1,000
Fin pitch 1.4
Rows × Stages 4 × 14
Face area
m
2
0.29
Pipe type (Material) Grooved H-pin (Copper)
Fin
Type Slit (Aluminum)
Surface treatment Hydrophilic coating
Air filter (Option)
Model name UTD-LF25NA
Net material PP honeycomb
Enclosure
Material Galvanized steel sheet
Color
Dimensions
(H × W × D)
Net
mm
270 × 1,135 × 700
Gross 300 × 1,320 × 790
Weight
Net
kg
40
Gross 48
Connection pipe diameter
Liquid (Flare)
mm (in)
Ø 6.35 (Ø 1/4) Ø 9.52 (Ø 3/8)
Gas (Flare) Ø 12.70 (Ø 1/2) Ø 15.88 (Ø 5/8)
Drain hose
VP25
I.D.: Ø 25 (1); O.D.: Ø 32 (1-1/4)
NOTES:
Specifications are based on the following conditions:
Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
Pipe length: 7.5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
Protective function might work when using it outside the operation range.
*1: This value is “Cooling operation/Heating operation”.
*: Sound pressure level:
Measured values in manufacturer’s anechoic chamber.
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
2-8. Low static pressure duct type (High efficiency)
- (04-19) - 2. Specifications