3-3. Separation tube
Total cooling capacity of indoor unit (kW) Model name
19.6 or less UTP-AX054A
28.0 or less UTP-AX090A
28.1 to 56.0 UTP-AX180A
¢
Installation
Select the connections with the pipe diameter that match the selected pipe sizes from the Separation
tube, and cut them with a pipe cutter.
L
1/2L 0 to 3 mm
Joint pipe (Branch kit)
Field pipe
Standard cutting position:
1/2L
+3
-0
mm
C
onne
c
tion
s
NOTE: Insert the field pipe firmly until it touches the joint pipe (Separation tube).
When the pipe size of the Separation tube itself does not match, or when piping sizes differ ever if it
cuts the pipe, use attached reducer or attached expander.
Joint pipe
(Separation tube)
Field pipeReducer or
Expander
3-3. Separation tube - (06-42) - 3. Piping connection