Model name AUXA30GALH AUXA34GALH
Power supply 230 V ~ 50 Hz
Available voltage range 198—264 V
Capacity
Cooling
kW 9.0 10.0
Btu/h 30,700 34,100
Heating
kW 10.0 11.2
Btu/h 34,100 38,200
Input power W 59 77
Fan
Airflow rate
HIGH
m
3
/h (l/s)
1,600 (444) 1,750 (486)
MED 1,300 (361)
LOW 1,100 (306)
Type × Q'ty Turbo × 1
Motor output W 80
Sound pressure level*
HIGH
dB (A)
40 43
MED 38
LOW 33
Heat exchanger type
Dimensions
(H × W × D)
mm
252 × 2,153 × 13.3
252 × 2,087 × 13.3
252 × 2,021 × 13.3
Length 2,087
Fin pitch 1.3
Rows × Stages 3 × 12
Face area
m
2
0.52
Pipe type (Material) Grooved H-pin (Copper)
Fin
Type Slit (Aluminum)
Surface treatment Hydrophilic coating
Air filter
Type Anti-mold
Net material PP honeycomb
Enclosure
Material Galvanized sheet iron
Color
Dimensions
(H × W × D)
Net Main body
mm
288 × 840 × 840
Gross 360 × 960 × 985
Weight
Net
kg
27
Gross 33
Connection pipe diameter
Liquid (Flare)
mm (in)
Ø 9.52 (Ø 3/8)
Gas (Flare) Ø 15.88 (Ø 5/8)
Drain hose
VP25
I.D.: Ø 25 (1); O.D.: Ø 32 (1-1/4)
Cassette grille
(Option)
Model name
UTG-UGA-W
Color
White
Approximate color of Munsell N9.25/
Dimensions
(H × W × D)
Net
mm
50 × 950 × 950
Gross 115 × 1,020 × 1,000
Weight
Net
kg
5.5
Gross 8.5
NOTES:
Specifications are based on the following conditions:
Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
Pipe length: 7.5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
Protective function might work when using it outside the operation range.
*: Sound pressure level:
Measured values in manufacturer’s anechoic chamber.
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.