Installing
Tread the hose band through the joint hose and
secure the drain pump unit and indoor unit.
Hose band (Small)
Joint hose
Hose band (Big)
Loosen the nut on the indoor unit and hook the tip of the bracket.
Tighten the nut securely.
Make sure that the drain pump unit is not slanted.
0-5 mm
0-5 mm
AIR
AIR
Ceiling
Level meter
Level meter
Good
Bad
Good
Bad
Installing hose
Max. 1m
Downward
Vertical
Horizontal
Bend radius is 60 mm or more
Downward gradient of 1/50 to 1/100
Part: Hose
Upward
Trap
Vertical loop
Example of wrong construction
8-1. Drain pump unit for duct type - (10-29) - 8. Optional parts installation