Model name AUXK018GLEH AUXK024GLEH AUXK030GLEH AUXK034GLEH
Power supply 230 V ~ 50 Hz
Available voltage range 198—264 V
Capacity
Cooling
kW 5.6 7.1 9.0 10.0
Btu/h 19,100 24,200 30,700 34,100
Heating
kW 6.3 8.0 10.0 11.2
Btu/h 21,500 27,300 34,100 38,200
Input power W 40 47
Fan
Airflow rate
HIGH
m
3
/h (l/s)
1,420 (394) 1,440 (400)
MED—HIGH 1,360 (378) 1,400 (389)
MED 1,300 (361) 1,340 (372)
MED—LOW 1,270 (353) 1,300 (361)
LOW 1,200 (333) 1,280 (356)
QUIET 1,150 (319) 1,150 (319)
Type × Q'ty Turbo × 1
Motor output W 81
Sound pressure level*
HIGH
dB (A)
38 39
MED—HIGH 37 38
MED 36 37
MED—LOW 35 36
LOW 34 35
QUIET 33
Heat exchanger type
Dimensions
(H × W × D)
mm
252 × 2,127 × 13.3
252 × 2,061 × 13.3
252 × 2,124 × 13.3
252 × 2,062 × 13.3
252 × 1,999 × 13.3
Length 2,094 2,062
Fin pitch 1.2 1.3
Rows × Stages 2 × 12 3 × 12
Pipe type (Material) Grooved H-pin (Copper)
Fin
Type Slit (Aluminum)
Surface treatment Hydrophilic coating
Air filter Net material PP honeycomb
Enclosure
Material Galvanized sheet iron
Color
Dimensions
(H × W × D)
Net Main body
mm
288 × 840 × 840
Gross 340 × 960 × 950
Weight
Net
kg
26.5 29.5
Gross 31.5 34.0
Connection pipe diameter
Liquid (Flare)
mm (in)
Ø 6.35 (Ø 1/4) Ø 9.52 (Ø 3/8)
Gas (Flare) Ø 12.70 (Ø 1/2) Ø 15.88 (Ø 5/8)
Drain hose
VP25
I.D.: Ø 25 (1); O.D.: Ø 32 (1-1/4)
Cassette grille
(Option)
Material
PS
Color
UTG-UKC-W:
White
Approximate color of Munsell N9.25/
UTG-UKA-B:
Black
Approximate color of Munsell N2/
Dimensions
(H × W × D)
Net
mm
53 × 950 × 950
Gross 110 × 1,000 × 1,010
Weight
Net
kg
6.0
Gross 10.0
NOTES:
Specifications are based on the following conditions:
Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
Pipe length: 7.5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
Protective function might work when using it outside the operation range.
*: Sound pressure level:
Measured values in manufacturer’s anechoic chamber.
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
2-3. Circular flow cassette type
- (04-10) - 2. Specifications
INDOOR
UNITS
INDOOR
UNITS

Table of Contents