Model name AUXV014GLEH AUXV018GLEH AUXV024GLEH
Power supply 230 V ~ 50 Hz
Available voltage range 198—264 V
Capacity
Cooling
kW 4.5 5.6 7.1
Btu/h 15,400 19,100 24,200
Heating
kW 5.0 6.3 8.0
Btu/h 17,100 21,500 27,300
Input power W 38 56 99
Fan
Airflow rate
HIGH
m
3
/h (l/s)
720 (200) 890 (247) 1,150 (319)
MED—HIGH 660 (183) 840 (233) 1,020 (283)
MED 630 (175) 770 (214) 940 (261)
MED—LOW 600 (167) 710 (197) 790 (219)
LOW 580 (161) 660 (183) 700 (194)
QUIET 550 (153) 580 (161) 610 (169)
Type × Q'ty Sirocco × 4
Motor output W 80
Sound pressure level*
HIGH
dB (A)
37 44 49
MED—HIGH 36 43 47
MED 35 40 45
MED—LOW 34 38 42
LOW 33 36 39
QUIET 32 34 36
Heat exchanger type
Dimensions
(H × W × D)
mm
336 × 890 × 26.6
336 × 890 × 26.6
126 × 890 × 13.3
Length 890
Fin pitch 1.3 1.3, 1.45
Rows × Stages 2 × 16 2 × 16, 1 × 6
Pipe type (Material) Grooved H-pin (Copper)
Fin
Type Slit (Aluminum)
Surface treatment Hydrophilic coating
Air filter Net material PP honeycomb
Enclosure
Material Galvanized sheet iron
Color
Dimensions
(H × W × D)
Net Main body
mm
198 × 1,190 × 570
Gross 305 × 1,530 × 695
Weight
Net
kg
26 27
Gross 36
Connection pipe diameter
Liquid (Flare)
mm (in)
Ø 6.35 (Ø 1/4) Ø 9.52 (Ø 3/8)
Gas (Flare) Ø 12.70 (Ø 1/2) Ø 15.88 (Ø 5/8)
Drain hose
VP25
I.D.: Ø 25 (1); O.D.: Ø 32 (1-1/4)
Cassette grille
(Option)
Model name
UTG-UNB-W
Color
White
Approximate color of Munsell N9.25/
Dimensions
(H × W × D)
Net
mm
43 × 1,360 × 620
Gross 150 × 1,495 × 735
Weight
Net
kg
8.5
Gross 14
NOTES:
Specifications are based on the following conditions:
Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
Pipe length: 7.5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
Protective function might work when using it outside the operation range.
*: Sound pressure level:
Measured values in manufacturer’s anechoic chamber.
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
2-5. One way flow cassette type
- (04-14) - 2. Specifications
INDOOR