Model name ARXC060GTEH ARXC072GTEH ARXC090GTEH ARXC096GTEH
Power supply 230 V ~ 50 Hz
Available voltage range 198—264 V
Capacity
Cooling
kW 18.0 22.4 25.0 28.0
Btu/h 61,400 76,400 85,300 95,500
Heating
kW 20.0 25.0 28.0 31.5
Btu/h 68,200 85,300 95,500 107,500
Input power W 730 681 819 838
Static pressure range Pa 100 to 250 0 to 300
Standard static pressure Pa 100 150
Fan
Airflow rate
HIGH
m
3
/h (l/s)
3,500 (972) 3,900 (1,083) 4,300 (1,195) 4,850 (1,347)
MED 3,000 (833) 3,300 (917) 4,000 (1,111) 4,250 (1,181)
LOW 2,460 (683) 3,000 (833) 3,500 (972) 3,600 (1,000)
Type × Q'ty Sirocco × 2
Motor output W 540 700 × 2
Sound pressure level*
HIGH
dB (A)
49 47 48 48
MED 45 43 46 45
LOW 42 40 44 42
Heat exchanger type
Dimensions (H × W × D)
mm
336 × 890 × 53.2 378 × 1,250 × 53.2 508 × 1,250 × 76.2
Length 890 1,250
Fin pitch 1.45 1.60
Rows × Stages 4 × 16 4 × 18 4 × 20
Face area
m
2
0.30 0.50 0.64
Pipe type (Material) Grooved H-pin (Copper)
Fin
Type (Material) Slit (Aluminum) Louver (Aluminum)
Surface treatment Hydrophilic coating
Air filter
Model name UTD-LF60KA
—
Net material PP honeycomb
Enclosure
Material Galvanized sheet iron
Color —
Dimensions
(H × W × D)
Net
mm
400 × 1,050 × 500 450 × 1,587 × 700 550 × 1,587 × 700
Gross 460 × 1,230 × 640 520 × 1,750 × 825 620 × 1,750 × 825
Weight
Net
kg
46 84 105
Gross 51 100 125
Connection pipe diameter
Liquid
mm (in)
Ø 9.52 (Ø 3/8)
(Flare)
Ø 9.52 (Ø 3/8)
(Brazing)
Gas
Ø 19.05 (Ø 3/4)
(Flare)
Ø 22.22 (Ø 7/8)
(Brazing)
Drain hose
VP25
I.D.: Ø 25 (1); O.D.: Ø 32 (1-1/4)
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Pipe length: 7.5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
2-10. High static pressure duct type
- (04-22) - 2. Specifications
INDOOR
UNITS
INDOOR
UNITS