Model name
AGE012GCEH AGE014GCEH
Power supply 230 V ~ 50 Hz
Available voltage range 198—264 V
Capacity
Cooling
kW 3.6 4.0
Btu/h 12,300 13,600
Heating
kW 4.0 4.5
Btu/h 13,600 15,400
Input power W 22 29
Fan
Airflow rate
HIGH
m
3
/h (l/s)
590 (164) 670 (186)
MED—HIGH 520 (144) 590 (164)
MED 470 (131) 520 (144)
MED—LOW 420 (117) 450 (125)
LOW 390 (108)
QUIET 340 (94)
Type × Q'ty Cross flow × 2
Motor output W 16 × 2
Sound pressure level*
HIGH
dB (A)
42 46
MED—HIGH 39 42
MED 37 39
MED—LOW 35 36
LOW 33
QUIET 30
Heat exchanger type
Dimensions (H × W × D)
mm
378 × 550 ×26.6
Length 550
Fin pitch 1.2
Rows × Stages 2 × 18
Pipe type (Material) Grooved H-pin (Copper)
Fin
Type Slit (Aluminum)
Surface treatment Hydrophilic coating
Air filter Net material PP plain weave
Enclosure
Material Plastic
Color
White
Approximate color of Munsell 5Y 9/0.5NN
Dimensions
(H × W × D)
Net
mm
600 × 740 × 200
Gross 700 × 820 × 310
Weight
Net
kg
14.5
Gross 18.5
Connection pipe diameter
Liquid (Flare)
mm (in)
Ø 6.35 (Ø 1/4)
Gas (Flare) Ø 12.70 (Ø 1/2)
Drain hose I.D.: Ø 13.8 (9/16); O.D.: Ø 15.8 to Ø 16.7 (5/8 to 11/16)
EV kit (Option) UTR-EV14XB
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Pipe length: 7.5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
2-12. Compact floor type (EEV external model)
- (04-26) - 2. Specifications
INDOOR
UNITS
INDOOR