Model name
ASE012GCEH ASE014GCEH
Power supply 230 V ~ 50 Hz
Available voltage range 198—264 V
Capacity
Cooling
kW 3.6 4.0
Btu/h 12,300 13,600
Heating
kW 4.0 4.5
Btu/h 13,600 15,400
Input power W 25 36
Fan
Airflow rate
HIGH
m
3
/h (l/s)
690 (192) 800 (222)
MED—HIGH 610 (169) 740 (206)
MED 560 (156) 680 (189)
MED—LOW 530 (147) 610 (169)
LOW 470 (131) 550 (153)
QUIET 330 (92)
Type × Q'ty Cross flow × 1
Motor output W 30
Sound pressure level*
HIGH
dB (A)
40 44
MED—HIGH 37 42
MED 35 40
MED—LOW 33 37
LOW 30 34
QUIET 24
Heat exchanger type
Dimensions
(H × W × D)
mm
Main: 320 × 630 × 20
Sub: 84 × 630 × 13.3
Length 630
Fin pitch
Main: 1.1
Sub: 1.4
Rows × Stages
Main: 2 × 20
Sub: 1 × 4
Face area —
Pipe type (Material) Grooved H-pin (Copper)
Fin
Type Slit (Aluminum)
Surface treatment Hydrophilic coating
Air filter Net material PP honeycomb
Enclosure
Material Plastic
Color
White
Approximate color of Munsell N9.25/
Dimensions
(H × W × D)
Net Main body
mm
268 × 840 × 203
Gross 270 × 884 × 336
Weight
Net
kg
8.5
Gross 11
Connection pipe diameter
Liquid (Flare)
mm (in)
Ø 6.35 (Ø 1/4)
Gas (Flare) Ø 12.70 (Ø 1/2)
Drain hose I.D.: Ø 13.8 (9/16); O.D.: Ø 15.8 to Ø 16.7 (5/8 to 11/16)
EV kit (Option) UTR-EV14XB
NOTES:
• Specifications are based on the following conditions:
– Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
– Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
– Pipe length: 7.5 m, Height difference: 0 m. (Between outdoor unit and indoor unit.)
• Protective function might work when using it outside the operation range.
• *: Sound pressure level:
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
2-16. Wall mounted type (EEV external model)
- (04-33) - 2. Specifications
INDOOR
UNITS
INDOOR
UNITS