¢ Installation space requirement
Unit: mm
Strong and durable ceiling
3,000 or more
1,800 to
H2
1,000 or more
Floor
Obstruction
1,500 or moreH1
Model name H1: Attic height (mm)
AUXM018-030GLEH 256 or more
AUXK018-054GLEH 298 or more
Be sure to make function setting with the remote controller according to the installed ceiling height.
H2: The maximum height from floor to ceiling (mm)
Ceiling height
Model name
AUXM018-030GLEH AUXK018-034GLEH AUXK036-054GLEH
Standard 3,000 3,200
High ceiling 3,500 3,600 4,200
Installation notices
When installing the indoor unit, be careful about the maintenance space.
To set “3-direction”, Air outlet shutter plate (option) must be installed, and the “outlet-direction”
need to be switched to “3-way” by the remote controller.
100 or more
4 directions
3 directions
Piping position
In 3-way outlet mode, changing of ceiling height setting by function setting 20 is prohibited. (Ceil-
ing height setting [function setting 20] is allowed to be changed only in 4-way outlet mode.)
Use the Insulation kit for high humidity (option), when the condition under the roof is over 80% in
humidity and over 30°C in temperature. Otherwise, there is a risk of condensation on the ceiling.
4-3. Circular flow cassette type
- (04-43) - 4. Dimensions
INDOOR
UNITS
INDOOR