¢ Central control
Group Remote Controller
Up to 8 remote controller groups can be controlled with one group remote controller.
Up to 4 Group remote controllers can be connected to a single network convertor (UTY-VGGXZ1).
One network convertor (UTY-VGGXZ1) is allowed 2 refrigerant systems.
Up to a total of 16 network convertors, central remote controllers and touch panel controllers, group remote
controller and network convertor for LONWORKS can be connected to single VRF network system.
1 2
Wired remote
controller
Wireless remote
controller
Simple remote controller
Group remote controller
Network convertor
Wired remote controller
Up to 8 remote controller groups
Meeting room
Lobby
Guest room
Central Remote Controller
Up to 100 indoor units / 16 groups can be controlled with one central remote controller.
The sum total of the Touch panel controller, Central remote controller, Network convertor for Group remote
controller , Modbus convertor and Network convertor for LONWORKS is a maximum of 16.
Commercial building (Small class)
Central
remote
controller
Up to 16
Central Remote
controllers
Up to 100
outdoor units
To outdoor
units
Up to 100 indoor units
1-2. System configuration examples - (05-4) - 1. Control system
CONTROL
SYSTEM
CONTROL
SYSTEM