System diagrams
When one group remote controller is connected:
Network convertor
(UTY-VGGXZ1)
When multiple group remote controllers are connected:
Remote
controller cable
Network convertor
(UTY-VGGXZ1)
Network convertor
(UTY-VGGXZ1)
NOTES:
Total remote controller cable length: Max. 100 m
Connectable group remote controller: Max. 4 units/convertor
Use of a terminal box is recommended when a junction is made in the wiring.
¢
Electrical wiring
G
1 2 3
L N
POWER
X1 X2
TRANSMISSION
Y1 Y2 Y3 J1
REMOTE INDOOR UNIT
REMOTE CONTROLLER LINE
J2 J3
Group
Remote
Controller
Transmission
Line
Transmission
Line
SWITCH
FUSE (3 A)
1
Φ
50/60 Hz
208-240 V
Power Supply
NETWORK CONVERTOR
Group remote controller cable
(Locally purchased) cross-section 0.33 mm
2
Polar 3-core, Shielded.
1. 12 V
2. Signal
3. COM
¢ Dimensions
Unit: mm
120
120
Name plate (Accessory)
(84 x 21)
83.5
15.3
63.5
Hole
45.3
4.5
9
12.5
Hole x 2
Hole x 3
4.5
4.5
6
30
33.5
23
18
C
Front View Side View Rear View