¢ Dimensions
Unit: mm
For M4 × 16 mm
screws
Hole pitch
3-Ø4.5
98
2-Ø10
121 10
43
Hole: 2 x 8
117
140
For open case
30
25
For code (> Ø7)
Hole: 2-Ø7
For code (≤ Ø7)
2-Ø8
For code (> Ø5)
Hole: 2-Ø5
For code (≤ Ø5)
25
30
¢ Specifications
Input power W 2
Temperature
Operating °C 0 to 46
Packaged °C -10 to 60
Humidity Packaged %
0 to 95 (RH)
No condensation
Dimensions (H × W × D) mm 140 × 117 × 43
Weight g 250
Wiring specifications
Use Cable size Wire type Remarks
Transmission cable
0.33 mm
2
(22 AWG)
LEVEL 4 (NEMA)
Non-polar 2 core, twisted pair
solid core shielded
LonWorks compatible cable
Remote controller
cable
(2-wire type)
0.33 to 1.25 mm
2
(22 to 16 AWG)
Non-polar 2 core
Use sheathed PVC cable or
shielded cable in accordance
with the regional cable standard.
Remote controller
cable
(3-wire type)
0.33 mm
2
(22 AWG)
Polar 3 core
3-1. Network converter (UTY-VTGX) - (05-119) - 3. Adaptor/Convertor units