Control and monitoring items with object types
Function name
Category BACnet
object
type*
1
Remarks
Target Monitor Control
Operation setting*
2
Bat BO
Operation mode Bat MO
Temperature setting Bat AO
Fan speed Bat MO
R/C prohibition Bat MO
Gateway GW D No monitor/control difference
Representative error GW BI Gateway, Lon communication
Error code GW MI
Gateway, Lon communication
Error codes to signal gateway status
will be agreed with FGL during
development.
Energy saving status/setting GW BI/BO
Existence check In BI
Temperature status/setting In AI/AO
Operation status/setting In BI/BO
Operation mode status/setting In MI/MO
Fan speed status/setting In MI/MO
Suction/Room temperature In AI
Representative error In BI
Error code In MI
Temperature H/L limit status/
setting
In AI/AO
H/L limit per 3 operation Mode:
HEAT, COOL-DRY, and AUTO
Temperature limit validity
status/setting
In BI/BO
Filter sign status/reset In BI/BO Only reset for control
Forced thermo off status/
setting*
3
In BI / BO
Emergency stop In BI
R/C prohibition status/setting In MI/MO
Vertical fan status/setting In MI/MO
Horizontal fan status/setting In MI/MO
Managed mode In MI
Outdoor unit save status/
setting
Out MI/MO
Low noise operation status/
setting
Out MI/MO Monitor not supported by all
Representative error Out BI
Error code Out MI
Forced off status/setting Out BI/BO