EasyManua.ls Logo

Fujitsu AJ 126LELDH Series - Page 697

Fujitsu AJ 126LELDH Series
1092 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
¢ Specifications
Input power W 0.6
Temperature
Operating °C 0 to 46
Packaged °C -10 to 60
Humidity Packaged %
0 to 95 (RH)
No condensation
Dimensions (H × W × D) mm 43 × 117 × 140
Weight g 250
Wiring specifications
Use Cable size Wire type Remarks
Remote controller
cable
(2-wire type)
0.33 to 1.25 mm
2
(22 to 16 AWG)
Sheathed PVC cable*
Non-polar 2 core, twisted pair
Maximum cable length: 500 m
Remote controller
cable
(3-wire type)
0.33 mm
2
(22 AWG)
Polar 3 core, twisted pair
Maximum cable length: 25 m
External input cable
0.33 to 1.25 mm
2
(22 to 16 AWG)
2 core, twisted pair
Maximum cable length: 50 m
*: Use sheathed cable in accordance with local rules for remote controller cable.
3-13. External switch controller (UTY-TERX) - (05-197) - 3. Adaptor/Convertor units