Pipe size table “A”
Between outdoor unit and the first separation tube (header)
Standard
HP
Outdoor unit
model code
Outdoor unit cooling
capacity
Outside diameter
Liquid pipe Gas pipe
kW mm (in)
8 072 22.4 9.52 (3/8) 19.05 (3/4)
10 096 28.0 9.52 (3/8) 22.22 (7/8)
12 108 33.5 12.70 (1/2) 28.58 (1-1/8)
14 126 40.0 12.70 (1/2) 28.58 (1-1/8)
16 144 45.0 12.70 (1/2) 28.58 (1-1/8)
18 162 50.0 12.70 (1/2) 28.58 (1-1/8)
Condition 1: Total indoor unit capacity ratio > 110%
HP
Outdoor unit
model code
Outdoor unit cooling
capacity
Outside diameter
Liquid pipe Gas pipe
kW mm (in)
8 072 22.4 9.52 (3/8) 19.05 (3/4)
10 096 28.0 12.70 (1/2) 22.22 (7/8)
12 108 33.5 12.70 (1/2) 28.58 (1-1/8)
14 126 40.0 12.70 (1/2) 28.58 (1-1/8)
16 144 45.0 12.70 (1/2) 28.58 (1-1/8)
18 162 50.0 12.70 (1/2) 28.58 (1-1/8)
Condition 2: Between outdoor unit and first separation tube or header > 70 m (229 ft)
HP
Outdoor unit
model code
Outdoor unit cooling
capacity
Outside diameter
Liquid pipe Gas pipe
kW mm (in)
8 072 22.4 12.70 (1/2) 22.22 (7/8)
10 096 28.0 12.70 (1/2) 22.22 (7/8)
12 108 33.5 12.70 (1/2) 28.58 (1-1/8)
14 126 40.0 12.70 (1/2) 28.58 (1-1/8)
16 144 45.0 12.70 (1/2) 28.58 (1-1/8)
18 162 50.0 12.70 (1/2) 28.58 (1-1/8)
2-3. Pipe size - (06-23) - 2. Piping design
SYSTEM
DESIGN
SYSTEM
DESIGN