Pipe connection
CAUTION
Seal the pipe route hole with putty (locally purchased) such that there are no gaps. Small in-
sects or animals that are trapped in the outdoor unit may cause a short circuit in the electrical
component box.
To prevent pipe damage: do not make sharp bends in the pipe. Bend the pipe at a radius of 70
mm or greater.
To prevent pipe damage, avoid bending pipe many times at same part.
After completing all the pipe connection by brazing, perform the indoor unit pipe connection with
a flare joint.
When removing the pinch pipe or brazing the joint pipe, carry out the work while cooling down
the 3-way valve sufficiently.
Braze the joint pipe onto the 3-way valve at the liquid and gas side. Install the joint pipe appropri-
ately so that it can be connected easily with the main pipe.
Braze the joint pipe at the liquid and gas side with the main pipe.
NOTE:
Be sure to supply nitrogen when brazing.
Joint pipe A-L*¹
Joint pipe A*²
(accessory)
Joint pipe C*²
(accessory)
Joint pipe B-L*¹
Joint pipe B*²
(accessory)
Gas pipe
(locally purchased)
Liquid pipe
(locally purchased)
Joint pipe C*²
(accessory)
Liquid pipe
(locally purchased)
Gas pipe
(locally purchased)
NOTE:
*1: AJ108LELDH, AJ126LELDH, AJ144LELDH, and AJ162LELDH only
*2: AJ090LELDH only
3-1. Piping to outdoor unit - (06-37) - 3. Piping connection
SYSTEM
DESIGN
SYSTEM
DESIGN