Wiring example
CAUTION
Except for emergency, never turn off main as well as sub breaker of the indoor units during op-
eration. It will cause compressor failures as well as water leakage.
First, stop the indoor unit by operating the control unit, converter, or external input device, and
then cut the breaker.
Make sure to operate through the control unit, converter, or external input device.
When the breaker is designed, locate it at a place where the users cannot start and stop in the
daily work.
Regulation of wire size and circuit breaker differs from each locality, refer in accordance with the
regional standard.
Example 1: Using terminal board for indoor unit
AJ*144LE
AJ*162LE
AJ*090LE
AJ*072LE AJ*108LE AJ*126LE
Sub breaker
Sub breaker
Sub breaker
20 A
25 A
40 A
Power cable
6 mm
2
Power cable
6 mm
2
Power cable 10 mm
2
Sub breaker
Terminal board
Terminal board
Sub breaker
20 A
20 A
Indoor unit power supply
1ø 50 Hz 230 V
Outdoor unit power supply
3ø 50 Hz 400 V: AJ*xxxLE
Power cable
2.5 mm
2
Indoor
units
Indoor
units
Connected within
refrigerant system.
Total MCA ≤ 15 (A).
Total Sub breaker ≤ Main breaker
4-2. Power supply cable - (06-53) - 4. Wiring design
SYSTEM
DESIGN
SYSTEM
DESIGN